CONTROL NEWS YOU CAN USE SINCE 2006

Functional Devices — A Much Simpler Decision Than Picking a 2016 Presidential Primary Candidate

RIBMNLB-1 Functional Devices does it again! The RIBMNLB-1 gives you a simple and effective FAN SAFETY ALARM CIRCUIT control.

Alarm Fault Application: When the Latch/Fault Input is Closed (Normal state), the Relay is activated, and Red LED is Off. When Latch/Fault Input Opens (Alarm state), the Relay deactivates, and Red LED turns On. Until the Latch/ Fault Input is Closed AND either power is cycled or the RESET button is pressed, relay will remain in the Alarm state.

Notes:
• Fault conditions must last for at least 500 ms in order for the unit to go into Alarm state.
• Reset signal, whether via pushbutton or power cycling, must last for at least 30 ms in order to reset the device to go from Alarm state to Normal state.

Facebook
Twitter
LinkedIn
Pinterest

One Response

Leave a Reply

Your email address will not be published. Required fields are marked *

Stay In The Know. Join The Control Trends Newsletter.